Motor Calculator

Branch circuits for single- and three-phase motors of 1000 V and less: protection, conductors, grounding, raceway and control, NEC 2023

1

Motor

Table 430.250
Nameplate

2

Protection and control

Table 430.52(C)(1)

3

Conductors

430.22
Choose the sizes

Automatic finds the smallest size that meets the code. A chosen size is checked, and the grounding conductor grows with it (250.122(B)).

4

Installation

Voltage drop and maximum length

Report details

Motor branch circuit

    Branch circuit

    Motor control

    Maximum length by conductor size

    Raceway, to scale

    Conductors from NEC Chapter 9 Tables 5 and 8

    Inputs

    Basis

    NEC 2023, Article 430. Full-load current from Tables 430.248 and 430.250 (430.6(A)(1)); conductors by 430.22 and Table 430.22(E); short-circuit and ground-fault protection by 430.52 and Table 430.52(C)(1); overload protection by 430.32 with the nameplate current (430.6(A)(2)); controller by 430.83; disconnecting means by 430.102, 430.109 and 430.110; locked-rotor current from Table 430.251 or the code letter (Table 430.7(B)).

    Ampacity from Table 310.16 with Table 310.15(B)(1)(1) and Table 310.15(C)(1), limited by the terminal temperature (110.14(C)); conductor protection by Article 430 (240.4(G)). Equipment grounding conductor by 250.122(A), (B), (D) and (F). Raceway fill by Chapter 9 Tables 1, 4, 5 and 8.

    Voltage drop with Chapter 9 Table 9 at 75 °C: running at the full-load current and the running power factor; starting at the locked-rotor current and the starting power factor, for the branch circuit only. Voltage drop is not an NEC requirement for motor circuits (210.19(A) Informational Note No. 3).