Fault Current Calculator

Single- and three-phase, from the utility source to the end of the cable

1

System

2

Source

3

Transformer

More transformer settings

4

Secondary cable

Drag to turn. Double-click to reset.
    More cable settings
    Equipment rating at the end of the cable

    Finds the shortest cable that keeps every fault at the end within the rating.

    5

    Load

    for voltage drop

    Report details

    Available fault current

    Fault current

    Symmetrical rms, bolted faults

      Voltage drop

      Fault current along the cable

      Inputs
      Impedances and asymmetry ohms at the secondary voltage

      Basis

      Bolted, symmetrical rms faults by the ohmic method with complex impedances; prefault voltage at nominal; no motor or inverter contribution.

      Source impedance from the three-phase and phase-to-ground fault currents and X/R. Transformer impedance from %Z and X/R; single-phase 120 V faults use 1.5R + j1.2X of the full winding (half-winding approximation).

      Cable R and X from NEC Chapter 9 Table 9 (conduit); for direct buried and overhead cable, R from Table 9 and X from the geometry of the cable drawn. R corrected for temperature; phase-to-ground and phase-to-neutral faults return on the neutral.

      Voltage drop by the IEEE Std 141 formula; transformer regulation at nameplate impedance with the primary at nominal voltage.